- Type
- Boiler flue and chimney liner
- Location
- Staffordshire
- Status
- Completed
- System type
- Single wall stainless flue, flexible chimney liner
The job
Three boilers, one old chimney.
Three new condensing boilers into one common header, out through the existing brick chimney.
The bore was too tight to work inside and the school stayed open.
We lined the chimney from a boom MEWP and laid the header to a fall back to a drain.
Smoke tested and signed off on site.
3
320kW condensing boilers
Ø300
Common header and flexible liner
3°
Header fall back to a drain
4
Days to install
On site.
Site photographs
Scope
What we delivered.
- Site survey and route measurement
- Flue sizing calculations and drawings
- Job-specific RAMS
- Ø250 boiler connections and Ø300 common header
- Ø300 stainless flexible chimney liner
- Podium steps and a boom MEWP
- Smoke test and certificate of conformity
- Daily photo reports, completion report and O&M pack
Got a job like this?
Price normally within 24 hours of drawings or survey information.